Menu 7 − Analog I/O


Parameter07.001  Analog/Digital Input 1
Short descriptionDisplays the value of analog input 1
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit VolatileUpdate Rate4ms
Display FormatStandardDecimal Places2
CodingRO, FI, ND, NC, PT

The Analog input 1 can operate in different modes as defined by Analog Input 1 Mode (07.007) including current modes.

Voltage mode: Resolution of 11 bits. It is a single ended unipolar voltage input 0V-10V

Current mode: Resolution of 11 bits. It is a single ended unipolar 0-20mA

Digital mode: It indicates 0.00% or 100.00% depending on the state of the input.

The "Input Level" is defined for the different modes in the table below.

Mode Input Level
Voltage (Input Voltage/ 10V) x 100.00%
0-20mA (Input Current / 20mA) x 100.00%
20-0mA (20mA - Input Current) / 20mA x 100.00%
4-20mA (Input Current - 4mA) / 16mA x 100.00%
20-4mA

(20mA - Input Current) / 16mA x 100.00%

Digital 0.00% (corresponds to logical 0 if less than 9V) or 100.0% (corresponds to logical 1 if more than 11V)


Parameter07.002  Analog/Digital Input 2
Short descriptionDisplays the value of analog input 2
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit VolatileUpdate Rate4ms
Display FormatStandardDecimal Places2
CodingRO, FI, ND, NC, PT

The Analog input 2 can operate in different modes as defined by Analog/Digital Input 2 (07.002) including current modes.

Voltage mode: Resolution of 11 bits. It is a single ended unipolar voltage input 0V-10V if Analog Input 2 Thermistor Mode (07.045) = 0 or over temperature protection thermistor input if Analog Input 2 Thermistor Mode (07.045) > 0.

Current mode: Resolution of 11 bits. It is a single ended unipolar 0-20mA

Digital mode: It indicates 0.00% or 100.00% depending on the state of the input.

The "Input Level" is defined for the different modes in the table below.

Mode Input Level
Voltage (Input Voltage/ 10V) x 100.00%
0-20mA (Input Current / 20mA) x 100.00%
20-0mA (20mA - Input Current) / 20mA x 100.00%
4-20mA (Input Current - 4mA) / 16mA x 100.00%
20-4mA

(20mA - Input Current) / 16mA x 100.00%

Digital 0.00% (corresponds to logical 0 if less than 9V) or 100.0% (corresponds to logical 1 if more than 11V)


Parameter07.003  Analog/Digital Input/Output 3
Short descriptionDisplays the value of analog input 3
Minimum-100.00Maximum100.00
Default Units%
Type16 Bit VolatileUpdate Rate4ms
Display FormatStandardDecimal Places2
CodingRO, FI, ND, NC, PT

The Analog input/output 3 can operate in different modes as defined by Analog/Digital Input/Output 3 (07.003) including current modes.  See Analog I/O.

Voltage Input mode: Resolution of 11 bits. It is a single ended unipolar voltage input 0V-10V

Current mode: Resolution of 11 bits. It is a single ended unipolar 0-20mA

Digital mode: It indicates 0.00% or 100.00% depending on the state of the input.

Voltage Output mode: It is a single ended unipolar voltage output 0V-10V

The "Input/Output Level" is defined for the different modes in the table below.

Mode Input Level
Voltage input (Input Voltage/ 10V) x 100.00%
0-20mA (Input Current / 20mA) x 100.00%
20-0mA (20mA - Input Current) / 20mA x 100.00%
4-20mA (Input Current - 4mA) / 16mA x 100.00%
20-4mA

(20mA - Input Current) / 16mA x 100.00%

Digital 0.00% (corresponds to logical 0 if less than 9V) or 100.0% (corresponds to logical 1 if more than 11V)
Voltage output (Source Parameter Value]/ Source Parameter Value[Max]) x 100.00%. (0V-10V)

 


Parameter07.004  Stack Temperature
Short descriptionDisplays the temperature currently being measured on the heat sink
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

This parameter displays the temperature currently being measured on the heat sink. This is used as part of the drive thermal model, see Drive Over-temperature Alarm (10.018) for further details.


Parameter07.007  Analog Input 1 Mode
Short descriptionDefines the mode of analog input 1
Minimum-6Maximum7
Default6Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
-64-20mA Stop
-520-4mA Stop
-44-20mA Low
-320-4mA Low
-24-20mA Hold
-120-4mA Hold
00-20mA
120-0mA
24-20mA Trp
320-4mA Trp
44-20mA
520-4mA
6Voltage
7Digital

See Analog/Digital Input 1 (07.001).

The table below gives all the possible analog input modes.

In 4-20mA and 20-4mA current input modes the software detects a current input less than 3mA as a current loop loss and initiates an action depending on the mode set in the table below.

Value Mode Function

-6

4-20mA Stop 4-20mA with stop on current loop loss
-5 20-4mA Stop 20-4mA with stop on current loop loss
-4 4-20mA Low 4-20mA with switching to a low speed set in Analog Input 1 Preset on Current Loss (07.026) on current loop loss
-3 20-4mA Low 20-4mA with switching to a low speed set in Analog Input 1 Preset on Current Loss (07.026) on current loop loss
-2 4-20mA Hold 4-20mA with hold at level before loss on current loop loss (1)
-1 20-4mA Hold 20-4mA with hold at level before loss on current loop loss (1)
0 0-20mA 0-20mA
1 20-0mA 20-0mA
2 4-20mA Trip 4-20mA with An Input 1 Loss trip on current loss.
3 20-4mA Trip 20-4mA with An Input 1 Loss trip on current loss.
4 4-20mA 4-20mA with no action on current loop loss (input taken as 0%).
5 20-4mA 20-4mA with no action on current loop loss (input taken as 0%).
6 Voltage Voltage input

(1) Analog input level remains at the value it had in the previous sample before the current fell below 3mA.


Parameter07.008  Analog Input 1 Scaling
Short descriptionDefines the scaling factor of analog input 1
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

See Analog I/O.

Analog Input 1 Scaling (07.008) and Analog Input 1 Offset (07.030) have no effect if Analog Input 1 Mode (07.007) = 7 (Digital).

Analog/Digital Input 1 (07.001) is modified by Analog Input 1 Scaling (07.008), Analog Input 1 Offset (07.030) and Analog Input 1 Invert (07.009) before it is routed to its destination as follows:

A1O = Analog/Digital Input 1 (07.001) + Analog Input 1 Offset (07.030)
A1O is the value after the offset has been applied and is limited between -100.00% and 100.00%

A1S = A1O x Analog Input 1 Scaling (07.008)
A1S is the value after the scaling and the offset have been applied and is limited between -100.00% and 100.00%

If Analog Input 1 Invert (07.009) = 0 then A1I = A1S otherwise A1I = -A1S

A1I is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined by


Parameter07.009  Analog Input 1 Invert
Short descriptionInverts the signal for analog input 1
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See Analog Input 1 Scaling (07.008).


Parameter07.010  Analog Input 1 Destination A
Short descriptionDefines the output parameter for analog input 1
Minimum0.000Maximum30.999
Default1.036Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT

See Analog Input 1 Scaling (07.008).


Parameter07.011  Analog Input 2 Mode
Short descriptionDefines the mode for analog input 2
Minimum-6Maximum7
Default4Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
-64-20mA Stop
-520-4mA Stop
-44-20mA Low
-320-4mA Low
-24-20mA Hold
-120-4mA Hold
00-20mA
120-0mA
24-20mA Trp
320-4mA Trp
44-20mA
520-4mA
6Voltage
7Digital

This parameter takes onle effect if Analog Input 2 Thermistor Mode (07.045) = 0.

See Analog/Digital Input 2 (07.002).

The table below gives all the possible analogue input modes.

Value Mode Function

-6

4-20mA Stop Stop on loss
-5 20-4mA Stop Stop on loss
-4 4-20mA Low 4-20mA switching to equivalent of 4mA input current on loss(1). See Analog Input 2 Preset on Current Loss (07.027).
-3 20-4mA Low 20-4mA switching to equivalent of 4mA input current on loss(1). See Analog Input 2 Preset on Current Loss (07.027).
-2 4-20mA Hold 4-20mA hold at level before loss on current loss (2)
-1 20-4mA Hold 20-4mA hold at level before loss on current loss (2)
0 0-20mA 0-20mA
1 20-0mA 20-0mA
2 4-20mA Trip 4-20mA trip on current loss (1), (3)
3 20-4mA Trip 20-4mA trip on current loss (1), (3)
4 4-20mA 4-20mA no action on loss (1)
5 20-4mA 20-4mA no action on loss (1)
6 Voltage Voltage
7 Digital Digital

(1) Analogue input level is 0.00% if the current is below 3mA.

(2) Analogue input level remains at the value it had in the previous sample before the current fell below 3mA.

(3) A An Input 2 Loss is initiated if the current falls below 3mA.


Parameter07.012  Analog Input 2 Scaling
Short descriptionDefines the scaling factor for analog input 2
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

See Analog I/O.

Analog/Digital Input 2 (07.002) is modified by Analog Input 2 Scaling (07.012)Analog Input 2 Offset (07.031) and Analog Input 2 Invert (07.013) before it is routed to its destination as follows:

A2O = Analog/Digital Input 2 (07.002)+ Analog Input 2 Offset (07.031)
A2O is the value after the offset has been applied and is limited between 0.00% and 100.00%

A2S = A2O x Analog Input 2 Scaling (07.012)
A2S is the value after the scaling and the offset have been applied and is limited between 0.00% and 100.00%

If Analog Input 2 Invert (07.013) = 0 then A2I = A2S otherwise A2I = -A2S

A2I is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined by


Parameter07.013  Analog Input 2 Invert
Short descriptionInverts the signal for analog input 2
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See Analog Input 2 Scaling (07.012).


Parameter07.014  Analog Input 2 Destination A
Short descriptionDefines the output parameter for analog input 2
Minimum0.000Maximum30.999
Default1.037Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT

See Analog Input 2 Scaling (07.012).


Parameter07.015  Analog I/O 3 Mode
Short descriptionDefines the mode of analog input/output 3
Minimum-6Maximum8
Default8Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
-64-20mA Stop
-520-4mA Stop
-44-20mA Low
-320-4mA Low
-24-20mA Hold
-120-4mA Hold
00-20mA
120-0mA
24-20mA Trp
320-4mA Trp
44-20mA
520-4mA
6Voltage
7Digital
8Analogue Output

See Analog/Digital Input/Output 3 (07.003)

The table below gives all the possible analog input modes.

In 4-20mA and 20-4mA current input modes the software detects a current input less than 3mA as a current loop loss and initiates an action depending on the mode set in the table below.

Value Mode Function

-6

4-20mA Stop 4-20mA with stop on current loop loss
-5 20-4mA Stop 20-4mA with stop on current loop loss
-4 4-20mA Low 4-20mA with switching to a low speed set in Analog Input 3 Preset on Current Loss (07.040) on current loop loss
-3 20-4mA Low 20-4mA with switching to a low speed set in Analog Input 3 Preset on Current Loss (07.040) on current loop loss
-2 4-20mA Hold 4-20mA with hold at level before loss on current loop loss (1)
-1 20-4mA Hold 20-4mA with hold at level before loss on current loop loss (1)
0 0-20mA 0-20mA
1 20-0mA 20-0mA
2 4-20mA Trip 4-20mA with An Input 3 Loss trip on current loss.
3 20-4mA Trip 20-4mA with An Input 3 Loss trip on current loss.
4 4-20mA 4-20mA with no action on current loop loss (input taken as 0%).
5 20-4mA 20-4mA with no action on current loop loss (input taken as 0%).
6 Voltage Voltage input
7 Digital Digital input
8 Analog Output Analog output

(1) Analog input level remains at the value it had in the previous sample before the current fell below 3mA.


Parameter07.016  Analog Input 3 Scaling
Short descriptionDefines the scaling factor of analog input 3
Minimum0.000Maximum10.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW

See Analog I/O.

Input mode: Analog I/O 3 Mode (07.015) is -6 to 7.

Analog/Digital Input/Output 3 (07.003) is modified by Analog Input 3 Scaling (07.016), Analog Input 3 Offset (07.032) and Analog Input 3 Invert (07.017) before it is routed to its destination as follows:

A3O = Analog/Digital Input/Output 3 (07.003) + Analog Input 3 Offset (07.032)
A3O is the value after the offset has been applied and is limited between 0.00% and 100.00%

A3S = A3O x Analog Input 3 Scaling (07.016),
A3S is the value after the scaling and the offset have been applied and is limited between 0.00% and 100.00%

If Analog Input 3 Invert (07.017) = 0 then A3I = A3S otherwise A3I = -A3S

A3I is the value after the invert, scaling and offset have been applied and is the final value that is routed to the destination defined by

Output mode: Analog I/O 3 Mode (07.015) is 8.

See Analog Output 3 Source A (07.019).


Parameter07.017  Analog Input 3 Invert
Short descriptionInverts the signal for analog input/output 3
Minimum0Maximum1
Default0Units 
Type1 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See Analog Input 3 Scaling (07.016).


Parameter07.018  Analog Input 3 Destination A
Short descriptionDefines the output parameter for analog input 3
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, DE, PT

See Analog Input 3 Scaling (07.016).


Parameter07.019  Analog Output 3 Source A
Short descriptionDefines the input parameter for analog output 3
Minimum0.000Maximum30.999
Default0.000Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRW, PT

Analog Output 3 Source A (07.019) defines the source parameter for Analog Output 3.

The modulus of the value of the source parameter is then scaled with Analog Output 3 Scaling (07.020) and if the scaling is greater than 1.000 the value is clamped to 100.0% which corresponds to 10V.

The source parameter depends on Analog Output 3 Control (07.057).


Parameter07.020  Analog Output 3 Scaling
Short descriptionDefines the scaling factor for analog output 3
Minimum0.000Maximum40.000
Default1.000Units 
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places3
CodingRW, BU

See Analog Output 3 Source A (07.019).

An automatic scaling takes place when parameters are selected for an analog output. The maximum value of the parameter is used as the full scale value such that the analog output will be at full scale when the parameter value is at its maximum value. Some parameters do not reach their maximum values and so this parameter is provided for the user to apply further scaling and configure a bigger range of the analog output to be used.


Parameter07.026  Analog Input 1 Preset on Current Loss
Short descriptionDefines the current level held on analog input 1 current loss
Minimum4.00Maximum20.00
Default4.00UnitsmA
Type16 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places2
CodingRW

If Analog Input 1 Mode (07.007) is set to the 4-20mA Low or 20-4mA Low modes and the current falls below 3mA (Analog Input 1 Current Loop Loss (07.028) = 1) then the analog input 1 is held to Analog Input 1 Preset on Current Loss (07.026).

If the current rise above 4mA (Analog Input 1 Current Loop Loss (07.028) = 0) then the analog input 1 current is used as normal.


Parameter07.027  Analog Input 2 Preset on Current Loss
Short descriptionDefines the current level held on analog input 2 current loss
Minimum4.00Maximum20.00
Default4.00UnitsmA
Type16 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places2
CodingRW

If Analog Input 2 Mode (07.011) is set to the 4-20mA Low or 20-4mA Low modes and the current falls below 3mA (Analog Input 2 Current Loop Loss (07.029) = 1) then the analog input 2 is held to Analog Input 2 Preset on Current Loss (07.027).

If the current rise above 4mA (Analog Input 2 Current Loop Loss (07.029) = 0) then the analog input 2 current is used as normal.


Parameter07.028  Analog Input 1 Current Loop Loss
Short descriptionDisplays when analog input 1 falls below 3mA
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

See Analog Input 1 Preset on Current Loss (07.026).


Parameter07.029  Analog Input 2 Current Loop Loss
Short descriptionDisplays when analog input 2 falls below 3mA
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

See Analog Input 2 Preset on Current Loss (07.027).


Parameter07.030  Analog Input 1 Offset
Short descriptionDefines the offset of analog input 1
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 Scaling (07.008).


Parameter07.031  Analog Input 2 Offset
Short descriptionDefines the offset of analog input 2
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 2 Scaling (07.012).


Parameter07.032  Analog Input 3 Offset
Short descriptionDefines the offset of analog input 3
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 3 Scaling (07.016).


Parameter07.034  Inverter Temperature
Short descriptionDisplays the estimated junction temperature of the hottest power device within the drive inverter
Minimum-250Maximum250
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Inverter Temperature (07.034) shows the estimated junction temperature of the hottest power device within the drive inverter. If this temperature exceeds the switch down threshold defined for the power stage the switching frequency is reduced provided this feature has not been disabled (i.e. Auto-switching Frequency Change Disable (05.035) = 0) or the minimum switching frequency has not been reached. The switching frequency can be reduced from 12kHz to 6kHz to 3kHz, or from 16kHz to 8kHz to 4kHz to 2kHz. If the switching frequency has been reduced the drive will attempt to restore it to the required level when the Inverter Temperature (07.034) reduces.


Parameter07.035  Percentage Of d.c. Link Thermal Trip Level
Short descriptionDisplays the percentage of the maximum allowed temperature as estimated by the thermal model of the d.c. link components
Minimum0Maximum100
Default Units%
Type8 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Percentage Of d.c. Link Thermal Trip Level (07.035) gives the percentage of the maximum allowed temperature as estimated by the thermal model of the d.c. link components.


Parameter07.036  Percentage Of Drive Thermal Trip Level
Short descriptionDisplays the percentage of the thermal trip level of the temperature monitoring point or thermal model in the drive that is highest
Minimum0Maximum100
Default Units%
Type8 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Percentage Of Drive Thermal Trip Level (07.036)  gives the percentage of the thermal trip level of the temperature monitoring point or thermal model in the drive that is highest. This includes all thermal monitoring points Stack Temperature (07.004), Inverter Temperature (07.034) and Percentage Of d.c. Link Thermal Trip Level (07.035).

Percentage Of d.c. Link Thermal Trip Level (07.035) is used directly to give Percentage Of Drive Thermal Trip Level (07.036), but for all other monitored values which are temperatures this is given by

Percentage of thermal trip level = (Measured Temperature - 40°C) / (Trip temperature - 40°C) x 100%

The location of the measurement or the thermal model that is related to this temperature is given in Temperature Nearest To Trip Level (07.037). If Percentage Of Drive Thermal Trip Level (07.036) exceeds 90% Drive Over-temperature Alarm (10.018) is set to one. If Percentage Of Drive Thermal Trip Level (07.036) reaches 100% one of the trips given in the table below is initiated. The trip can be reset when the percentage of thermal trip level falls below 95%.

Temperature Trip
Inverter Temperature (07.034) OHt Inverter
 Stack Temperature (07.004) OHt Power
Percentage Of d.c. Link Thermal Trip Level (07.035) OHt dc bus


Parameter07.037  Temperature Nearest To Trip Level
Short descriptionDisplays the location or the model that corresponds to the value shown in Percentage Of Drive Thermal Trip Level
Minimum0Maximum29999
Default Units 
Type32 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

Temperature Nearest To Trip Level (07.037)  shows the location or the model that corresponds to the value shown in Percentage Of Drive Thermal Trip Level (07.036) in the form xxyzz as shown in the table below.

Source xx y zz
Control system 00 1 00: Inverter thermal model ( Inverter Temperature (07.034) )
Control system 00 2 00: D.c. link thermal model ( Percentage Of d.c. Link Thermal Trip Level (07.035) )
Power system 01 0 zz: Thermistor location defined by zz in the power system ( Stack Temperature (07.004)


Parameter07.040  Analog Input 3 Preset on Current Loss
Short descriptionDefines the current level held on analog input 3 current loss
Minimum4.00Maximum20.00
Default4.00Units 
Type16 Bit User SaveUpdate Rate4ms read
Display FormatStandardDecimal Places2
CodingRW

If Analog I/O 3 Mode (07.015) is set to the 4-20mA Low or 20-4mA Low modes and the current falls below 3mA (Analog Input 3 Current Loop Loss (07.041) = 1) then the analog input 3 is held to Analog Input 3 Preset on Current Loss (07.040)

If the current rise above 4mA (Analog Input 3 Current Loop Loss (07.041) = 0) then the analog input 3 current is used as normal.


Parameter07.041  Analog Input 3 Current Loop Loss
Short descriptionDisplays when analog input 3 falls below 3mA
Minimum0Maximum1
Default Units 
Type1 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, ND, NC, PT

See Analog Input 3 Preset on Current Loss (07.040).


Parameter07.045  Analog Input 2 Thermistor Mode
Short descriptionDefines the Analog input 2 thermistor mode
Minimum0Maximum3
Default0Units 
Type8 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW, TE

 

ValueTextDescription
0An/Dig InputInput
1Therm Short CctTemperature measurement input with short circuit detection (Resistance <50Ohm)
2ThermistorTemperature measurement input with Thermistor trip, but without short circuit detection
3Therm No TripTemperature measurement input with no trips

This parameter defines the Analogue Input 2 mode.

If Analog Input 2 Thermistor Mode (07.045) = 0 then the functionality is defined by Analog Input 2 Mode (07.011).

If Analog Input 2 Thermistor Mode (07.045) > 0 then the analogue input 2 is in Thermistor mode.


Parameter07.046  Thermistor Type
Short descriptionDefines the thermistor type when used
Minimum0Maximum4
Default0Units 
Type8 Bit User SaveUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRW, TE

ValueText
0DIN44081
1KTY84
2PT1000
3PT2000
4Other

Thermistor Type (07.046) defines the operation of the temperature feedback interface for Analogue Input 2 when Analog Input 2 Thermistor Mode (07.045) is 1, 2 or 3.

If Thermistor Type (07.046) = 0, the thermistor DIN44081 is designed to react like a temperature switch and therefore Thermistor Temperature (07.050) always reads 0.0°C.

If Thermistor Type (07.046) = 1 to 3 is selected, the digital input operation of the terminal is disabled.

If Thermistor Type (07.046) = 4, any thermistor can be used but Thermistor Temperature (07.050) always reads 0.0°C.


Parameter07.047  Thermistor Feedback
Short descriptionDisplays the measured resistance of the thermistor when used
Minimum0Maximum4000
Default Units
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, FI, ND, NC, PT

Thermistor Feedback (07.047) shows the measured resistance. If Analog Input 2 Thermistor Mode (07.045) is 2 then {Th} trip is initiated if the feedback value is higher than Thermistor Trip Threshold (07.048). The trip cannot be reset unless the feedback is below Thermistor Reset Threshold (07.049). The default values for Thermistor Trip Threshold (07.048) and Thermistor Reset Threshold (07.049) are the levels specified in the DIN 44082 standard.


Parameter07.048  Thermistor Trip Threshold
Short descriptionDefines the thermistor trip threshold when used
Minimum0Maximum4000
Default3300Units
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See Thermistor Feedback (07.047).


Parameter07.049  Thermistor Reset Threshold
Short descriptionDefines the thermistor reset threshold when used
Minimum0Maximum4000
Default1800Units
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places0
CodingRW

See Thermistor Feedback (07.047).


Parameter07.050  Thermistor Temperature
Short descriptionDisplays the temperature of the device based on the resistance to temperature characteristic for the specified device
Minimum-50Maximum300
Default Units°C
Type16 Bit VolatileUpdate RateBackground write
Display FormatStandardDecimal Places0
CodingRO, FI, ND, NC, PT

If a KTY84, PT1000 or PT2000 type device is selected for temperature feedback (i.e. Thermistor Type (07.046) = 1 to 3) then Thermistor Temperature (07.050) shows the temperature of the device based on the resistance to temperature characteristic specified for this device. Otherwise Thermistor Temperature (07.050) = 0.0.


Parameter07.051  Analog Input 1 Control
Short descriptionDefines the functionality of analog input 1
Minimum0Maximum5
Default0Units 
Type8 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places0
CodingRW

Value Description Analog Input 1 Destination B  (07.090)
0 User defined by Analog Input 1 Destination A (07.010) 00.000
1 Frequency reference 1 01.036
2 Frequency reference 2 01.037
3 Maximum reference clamp 01.006
4 Current limit 04.007
5 Torque reference 04.008

This offers a simple control of parameter Analog Input 1 Destination B  (07.090) to change the analog input 1 functionality.

If Analog Input 1 Control (07.051) is more than 0 then the destination is defined by Analog Input 1 Destination B  (07.090). The destination Analog Input 1 Destination B  (07.090) is written by Analog Input 1 Control (07.051) selection. (i.e. If Analog Input 1 Control (07.051) = 3 then Analog Input 1 Destination B  (07.090) = 01.006)

If Analog Input 1 Control (07.051) is 0 then then the destination is defined by Analog Input 1 Destination A (07.010).


Parameter07.052  Analog Input 2 Control
Short descriptionDefines the functionality of analog input 2
Minimum0Maximum5
Default0Units 
Type8 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places0
CodingRW

Value Description Analog Input 2 Destination B  (07.094)
0 User defined by Analog Input 2 Destination A (07.014) 00.000
1 Frequency reference 1 01.036
2 Frequency reference 2 01.037
3 Maximum reference clamp 01.006
4 Current limit 04.007
5 Torque reference 04.008

This offers a simple control of parameter Analog Input 2 Destination B  (07.094) to change the analog input 2 functionality.

If Analog Input 2 Control (07.052) is more than 0 then the destination is defined by Analog Input 2 Destination B  (07.094). The destination Analog Input 2 Destination B  (07.094) is written by Analog Input 2 Control (07.052) selection. (i.e. If Analog Input 2 Control (07.052)= 3 then Analog Input 2 Destination B  (07.094) = 01.006)

If Analog Input 2 Control (07.052) is 0 then then the destination is defined by Analog Input 2 Destination A (07.014).


Parameter07.053  Analog Input 3 Control
Short descriptionDefines the functionality of analog input 3
Minimum0Maximum5
Default0Units 
Type8 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places0
CodingRW

Value Description Analog Input 3 Destination B  (07.098)
0 User defined by Analog Input 3 Destination A (07.018) 00.000
1 Frequency reference 1 01.036
2 Frequency reference 2 01.037
3 Maximum reference clamp 01.006
4 Current limit 04.007
5 Torque reference 04.008

This offers a simple control of parameter Analog Input 3 Destination B  (07.098) to change the analog input 3 functionality.

If Analog Input 3 Control (07.053) is more than 0 then the destination is defined by Analog Input 3 Destination B  (07.098). The destination Analog Input 3 Destination B  (07.098) is written by Analog Input 3 Control (07.053) selection. (i.e. If Analog Input 3 Control (07.053)=3 then Analog Input 3 Destination B  (07.098) = 01.006)

If Analog Input 3 Control (07.053) is 0 then then the destination is defined by Analog Input 3 Destination A (07.018).


Parameter07.057  Analog Output 3 Control
Short descriptionDefines the functionality of analog output 3
Minimum0Maximum16
Default16Units 
Type8 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places0
CodingRW, BU

Value Description Analog Output 3 Source B (07.099)
0 User defined by Analog Output 3 Source A (07.019) 00.000
1 Post Ramp frequency reference (0 - ±VM_SPEED_FREQ_REF) 02.001
2 Pre Ramp frequency reference (0 - ±VM_SPEED_FREQ_REF) 01.003
3 Motor speed (0 - ±33,000) 05.004
4 Current output (0 - Full Scale Current Kc (11.061)) 04.001
5 Reserved Reserved
6 Percentage load (0 - ± User Current Maximum Scaling (04.024)) 04.020
7 Torque producing current (0 - Full Scale Current Kc (11.061)) 04.002
8 Voltage output (0 - VM_AC_VOLTAGE) 05.002
9 DC bus voltage (0 - VM_DC_VOLTAGE) 05.005
10 Analogue Input 1 (0 - ±100%) 07.001
11 Analogue Input 2 (0 - ±100%) 07.002
12 Power output (0 - ±VM_POWER) 05.003
13 Current limit (0 - ±VM_TORQUE_CURRENT) 04.018
14 Torque reference (0 - ±User Current Maximum Scaling (04.024)) 04.008
15 Reserved Reserved
16 External LED Driver N/A

This offers a simple control of parameter Analog Output 3 Source B (07.099) to change the analog output 3 source.

If Analog Output 3 Control (07.057) is 1 - 15 then the source is defined by Analog Output 3 Source B (07.099). The source Analog Output 3 Source B (07.099) is written by Analog Output 3 Control (07.057) selection. (i.e. If Analog Output 3 Control (07.057) = 13 then Analog Output 3 Source B (07.099) = 04.018)

If Analog Output 3 Control (07.057) is 0 then the source is defined by Analog Output 3 Source A (07.019)

If Analog Output 3 Control (07.057) is 16 then the analog output is used to control the illumination of 3 LED's on a flange option, coloured Red, Green and Yellow.

The Red LED is illuminated if the drive is in a tripped state, flashes if the drive is running with an alarm condition, and is off if the drive is healthy and not in an alarm condition.

The Green LED is illuminated if the input supply is healthy, flashes if the input supply is healthy and the drive output is active, and is off if the incoming supply is not healthy.

The Yellow LED is user defined and can be used to indicate any parameter by setting the appropriate parameter to be indicated in Analog Output 3 Source A (07.019).

The table below indicates the output voltage from analog output 3 for the defined LED states:

External LED Driver
Red Green Yellow Output Voltage (V)
OFF OFF OFF 0
OFF OFF ON 1.43
OFF ON ON 2.85
OFF ON OFF 4.32
ON ON OFF 5.76
ON ON ON 7.09
ON OFF ON 8.51
ON OFF OFF 10

 


Parameter07.061  Analog Input 1 Minimum Reference
Short descriptionDefines the minimum reference for analog input 1
Minimum0.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

The scaling function has no effect if Analog Input 1 Mode (07.007) = 7 (Digital).

Analog/Digital Input 1 (07.001) can be scaled and limited using the following parameters:

Parameters above can be selected to limit the range of Analog/Digital Input 1 (07.001) and also scale it between the minimum and maximum reference.

If Analog Input 1 Minimum Reference (07.061) ≥ Analog Input 1 Maximum Reference (07.063) then Ai1 = 0.00%whatever the input level.

Input Level is limited between Analog Input 1 At Minimum Reference (07.062) and Analog Input 1 At Maximum Reference (07.064)

Analog/Digital Input 1 (07.001) = [(Analog Input 1 At Maximum Reference (07.064) - Analog Input 1 At Minimum Reference (07.062)) / (Analog Input 1 Maximum Reference (07.063) - Analog Input 1 Minimum Reference (07.061))] x (Input level - Analog Input 1 Minimum Reference (07.061)) + Analog Input 1 At Minimum Reference (07.062).


Parameter07.062  Analog Input 1 At Minimum Reference
Short descriptionDefines the value of analog input 1 at minimum reference
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 Minimum Reference (07.061).


Parameter07.063  Analog Input 1 Maximum Reference
Short descriptionDefines the maximum reference for analog input 1
Minimum0.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 Minimum Reference (07.061).


Parameter07.064  Analog Input 1 At Maximum Reference
Short descriptionDefines the value of analog input 1 at maximum reference
Minimum-100.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 1 Minimum Reference (07.061).


Parameter07.065  Analog Input 2 Minimum Reference
Short descriptionDefines the minimum reference for analog input 2
Minimum0.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See graph in Analog Input 1 Minimum Reference (07.061).

Analog/Digital Input 2 (07.002) can be scaled and limited using the following parameters:

Parameters above can be selected to limit the range of Analog/Digital Input 2 (07.002) and also scale it between the minimum and maximum reference.

If Analog Input 2 Minimum Reference (07.065) ≥ Analog Input 2 Maximum Reference (07.067) then Ai2 = 0.00% whatever the input level.

Input Level is limited between Analog Input 2 At Minimum Reference (07.066) and Analog Input 2 At Maximum Reference (07.068)

Analog/Digital Input 2 (07.002) = [(Analog Input 2 At Maximum Reference (07.068) - Analog Input 2 At Minimum Reference (07.066))/(Analog Input 2 Maximum Reference (07.067) - Analog Input 2 Minimum Reference (07.065))] x (Input level - Analog Input 2 Minimum Reference (07.065))+ Analog Input 2 At Minimum Reference (07.066).


Parameter07.066  Analog Input 2 At Minimum Reference
Short descriptionDefines the value of analog input 2 at minimum reference
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 2 Minimum Reference (07.065).


Parameter07.067  Analog Input 2 Maximum Reference
Short descriptionDefines the maximum reference for analog input 2
Minimum0.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 2 Minimum Reference (07.065).


Parameter07.068  Analog Input 2 At Maximum Reference
Short descriptionDefines the value of analog input 2 at maximum reference
Minimum-100.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 2 Minimum Reference (07.065).


Parameter07.069  Analog Input 3 Minimum Reference
Short descriptionDefines the minimum reference for analog input 3
Minimum0.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See graph in Analog Input 1 Minimum Reference (07.061).

Analog/Digital Input/Output 3 (07.003) can be scaled and limited using the following parameters:

Parameters above can be selected to limit the range of Analog/Digital Input/Output 3 (07.003) and also scale it between the minimum and maximum reference.

If Analog Input 3 Minimum Reference (07.069) ≥ Analog Input 3 Maximum Reference (07.071) then Ai3 = 0.00% whatever the input level.

Input Level is limited between Analog Input 3 At Minimum Reference (07.070) and Analog Input 3 At Maximum Reference (07.072)

Analog/Digital Input/Output 3 (07.003) = [(Analog Input 3 At Maximum Reference (07.072)- Analog Input 3 At Minimum Reference (07.070))/(Analog Input 3 Maximum Reference (07.071)- Analog Input 3 Minimum Reference (07.069))] x (Input level - Analog Input 3 Minimum Reference (07.069) + Analog Input 3 At Minimum Reference (07.070).


Parameter07.070  Analog Input 3 At Minimum Reference
Short descriptionDefines the value of analog input 3 at minimum reference
Minimum-100.00Maximum100.00
Default0.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 3 Minimum Reference (07.069).


Parameter07.071  Analog Input 3 Maximum Reference
Short descriptionDefines the maximum reference for analog input 3
Minimum0.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 3 Minimum Reference (07.069).


Parameter07.072  Analog Input 3 At Maximum Reference
Short descriptionDefines the value of analog input 3 at maximum reference
Minimum-100.00Maximum100.00
Default100.00Units%
Type16 Bit User SaveUpdate RateBackground read
Display FormatStandardDecimal Places2
CodingRW

See Analog Input 3 Minimum Reference (07.069).


Parameter07.090  Analog Input 1 Destination B
Short descriptionDefines the secondary destination for analog input 1
Minimum0.000Maximum30.999
Default Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRO, DE, ND, NC, PT

See Analog Input 1 Destination A (07.010).


Parameter07.094  Analog Input 2 Destination B
Short descriptionDefines the secondary destination for analog input 2
Minimum0.000Maximum30.999
Default Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRO, DE, ND, NC, PT

See Analog Input 2 Destination A (07.014).


Parameter07.098  Analog Input 3 Destination B
Short descriptionDefines the secondary destination for analog input 3
Minimum0.000Maximum30.999
Default Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRO, DE, ND, NC, PT

See Analog Input 3 Destination A (07.018).


Parameter07.099  Analog Output 3 Source B
Short descriptionDefines the secondary source for analog output 3
Minimum0.000Maximum30.999
Default Units 
Type16 Bit User SaveUpdate RateDrive reset read
Display FormatStandardDecimal Places3
CodingRO, ND, NC, PT

See Analog Output 3 Source A (07.019).